Product Search

Search within a specific product category (e.g., Socket Distribution Boards) or individual model series (e.g., elBOX) belonging to that category.
Category/Model
We manufacture products with equipment specifications suitable for many European countries. They differ in the type of sockets, residual current and overcurrent circuit breakers, label language, and other national requirements.
Market
The submodel of a given model marked after the dash (e.g., elBOX-XL), is usually related to the size of the housing and/or version of the frame.Some products only have one submodel equivalent to the model, so the choice is then synonymous.Icons next to the filters are illustrative.Details can be found on our website in the relevant product sections. XS/S/M/L/XL - housing sizes; R - frame (more durable version of the frame); W - trolley.
Type/ Size
The elBOX and elCARRY distribution boards are available with different frame versions (e.g., elBOX-XL/XLR or elCARRY/-R). The stand is the standard, lighter version of the frame, in the elBOX models it is foldable. The HD frame ("R" in the type designation) is heavier and more durable version of the frame. The trolley ("W" in the designation) or the base foundation ("F" in the designation) are only available in special products. Details can be found on our website in the relevant product sections.
Frame type
The elBOX and elTOWER distribution boards are made as standard with ETI brand equipment with a short-circuit withstand rating of 10kA or optional ELS brand equipment with a 6kA rating. Smaller elCARRY and elCASE distribution boards are made as standard with ETI brand equipment with a 6kA rating, optionally with ELS 6kA equipment. The elPOWER distribution boards are equipped with Jean Mueller disconnectors. Individual products are made with different equipment.
Prot. equipment
The elBOX and elTOWER distribution boards are available in versions with a rated current of 32A, 63A, and 125A, with other values appearing in some cases. The elCARRY and elCASE distribution boards are available in 16A and 32A versions. The elPOWER distribution boards are available in 400A and 630A versions. The rated current usually corresponds to the inlet plug/main circuit breaker.
Current / Power
The elBOX and elTOWER distribution boards are typically equipped with a main switch (switch disconnector) with a lever extended outside the housing. Its rated current usually corresponds to the rated current of the distribution board. The switch is required in versions powered by connection terminals. In versions powered by a CEE plug there is no such requirement and some of these versions do not have a main switch. The elCARRY and elCASE distribution boards do not have a main switch. The elPOWER distribution boards have a fuse switch disconnector for the power inlet field.
Main switch
The elBOX and elTOWER distribution boards are powered by a CEE 32A/63A/125A panel plug or terminal connections (each enclosure size offers different options), sometimes using a cable with a plug. The elCARRY distribution boards are powered by a cable with a CEE 16A/32A plug, and some special versions are powered by a CEE 16A/32A panel plug. The elCASE distribution boards are powered by a cable with a CEE 16A/32A plug or a CEE 16A/32A panel plug, with special versions available featuring a cable gland for stationary mounting. Details can be found on our website in the relevant product sections. FV - plug with a phase inverter.
Power inlet
Distribution boards with metering are equipped with a modular MID electronic meter. For distribution boards up to 100A, this is a direct measurement, while for 125A, it is a semi-direct measurement with current transformers. Direct meters are from the ELS brand, and semi-direct meters depend on the equipment options: for 6kA, ELS, and for 10kA, Socomec. Distribution boards in the elBOX-LM enclosure have a meter panel but are not equipped with a meter.
Measurement kWh
The number of of CEE 125A 5P (three-phase) outlets, including 4P outlets found in some versions, as well as 4P/5P outlets with a PE contact position other than 6h (e.g., Norway). The filter specifies the exact number of outlets, without the option "or more."
CEE sockets 125A-5P
The number of CEE 63A 5P (three-phase) outlets, including 4P outlets found in some versions, as well as 4P/5P outlets with a PE contact position other than 6h (e.g., Norway). The filter specifies the exact number of outlets, without the option "or more."
CEE sockets 63A-5P
The number of CEE 32A 5P (three-phase) outlets, including 4P outlets found in some versions, as well as 4P/5P outlets with a PE contact position other than 6h (e.g., Norway). The filter specifies the minimum number of outlets, with the option "or more."
CEE sockets 32A-5P
The number of CEE 16A 5P (three-phase) outlets, including 4P outlets found in some versions, as well as 4P/5P outlets with a PE contact position other than 6h (e.g., Norway). The filter specifies the minimum number of outlets, with the option "or more."
CEE sockets 16A-5P
The number of CEE 16A 3P (industrial/camping) outlets, including 3P outlets with a PE contact position other than 6h (e.g., UK). The filter specifies the minimum number of outlets, with the option "or more."
CEE sockets 16A-3P
The number of 230V (standard "household") outlets, including outlets regardless of the version: GK - Polish/French with a grounding pin (type E); GS - German/Scandinavian "Schuko" (type F), also in the special VDE-0620-1:2010 version; GD - Danish (type K); GC - Swiss (type J/T23) and others. The filter specifies the minimum number of outlets, with the option "or more."
GS 230V sockets
The ACS elBOX and elTOWER distribution boards are equipped as standard with residual current devices (RCDs) in a minimum quantity to allow their operation without overloading. This quantity depends on the rated current and socket configuration. There are versions of the distribution boards with the same socket configuration but an increased number of RCDs for separating sockets on individual circuits. Smaller elCARRY/elCASE distribution boards have versions with RCDs and, alternatively, versions without them (in such cases, they must be powered from a socket protected by an RCD).
RCD protection
The number of terminal outlets with an NH3 630A fuse switch disconnectors are found in the main/distribution boards elPOWER. The filter specifies the exact number of outlets, without the option "or more."
Outlets NH3 630A
The number of terminal outlets with an NH2 400A fuse switch disconnectors are found in the main/distribution boards elPOWER. The filter specifies the exact number of outlets, without the option "or more."
Outlets NH2 400A
The number of terminal outlets with an NH1 250A fuse switch disconnectorsh are found in the main/distribution boards elPOWER. The filter specifies the exact number of outlets, without the option "or more."
Outlets NH1 250A
The number of terminal outlets with an NH00/000 160A fuse switch disconnectors are found in the main/distribution boards elPOWER and in some versions of the elBOX distribution boards. The filter specifies the exact number of outlets, without the option "or more."
Outlets NH00 160A
The length of the switchboard's power supply cord or the total length of the extension cord/adapter. Measured as the actual length of the cable used in the product, not the length of the product itself.
Cable length
Selection of the type, number of conductors, and cross-section of the power supply cable for the distribution board or extension cord. Most of the cables we use are of the H07RN-F (OnPD) type, suitable for construction sites. The cross-sections are matched to the rated currents but also have available alternatives for both minimum and increased cross-sectional areas.
Cable type
Less commonly used outlets, which do not appear in separate filters (and the type designation of the distribution board), e.g., single-phase outlets 32-125A. Also, special options for standard outlets, such as the IP67 version of 16-32A outlets. The option "outlet 16A-5P IP67" refers to 16A-5P outlets, the quantity of which can be selected using a separate filter.
Special circuits
Results per page:
10 wyników na stronie
Number of products found: 771 Number of products found: 771 Number of products found: 771 No products found
Filters Sort results
Reset Apply
Product
- Product datasheet- Compare- Inquiry
Preview image
Frame type /Material
Parameters
Power inlet
Measurement kWh
Outlets
RCDprotection
ACS elBOX-L
Item No.
70403010
Type:
Z63-002106 10kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
0
2
1
0
6
1
0
ACS elBOX-L
Item No.
70406010
Type:
Z63-002206 10kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
0
2
2
0
6
1
0
ACS elBOX-L
Item No.
70406310
Type:
Z63-002206 v3 10kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
0
2
2
0
6
2
3
ACS elBOX-L
Item No.
70406410
Type:
Z63-002206 v4 10kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x95 mm2
no
-
125A63A32A16A16A
GK
0
0
2
2
0
6
2
3
ACS elBOX-L
Item No.
70410412
Type:
Z63-00220C v4 6kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
6 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
0
2
2
0
12
1
3
ACS elBOX-L
Item No.
70427017
Type:
Z63-012209 DK
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GD
0
1
2
2
0
9
2
0
ACS elBOX-L
Item No.
70445010
Type:
Z63-011106 10kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
1
1
1
0
6
2
0
ACS elBOX-L
Item No.
70484210
Type:
Z63-002260 v2 10kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
10 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
0
2
2
6
0
Special circuits
Additional special circuits. See product datasheet.
1
0
ACS elBOX-L
Item No.
70484212
Type:
Z63-002260 v2 6kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
6 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
no
-
125A63A32A16A16A
GK
0
0
2
2
6
0
Special circuits
Additional special circuits. See product datasheet.
1
0
ACS elBOX-L
Item No.
70484312
Type:
LZ63-002260 v3 6kA
Stand
/
stainless steel
TN-S
3/N/PE
In=
63 A
Sn=
43 kVA
Un=
400 V
f=
50 Hz
Inc=
6 kA
cord:
none
main
switch
Al/Cu terminals
63A
5x50 mm2
yes
-
125A63A32A16A16A
GK
0
0
2
2
6
0
Special circuits
Additional special circuits. See product datasheet.
1
0
1278
Scroll to Top